Corona Power Loss in HVDC Transmission Lines
Definition
Corona power loss is energy dissipated as heat, light, sound, and chemical action (ozone) when the electric field around a high-voltage conductor exceeds the dielectric strength of air (~30 kV/cm), causing partial ionization.
Mechanism in HVDC
- High surface gradient: DC voltage creates a constant radial electric field. Sharp points, water droplets, or contamination enhance local field strength.
- Electron avalanche: Free electrons accelerate, ionizing neutral molecules via collision. Positive ions drift to conductor; electrons to corona sheath.
- Current & loss: The ionization current represents real power loss: P_c = K * f * V^2 * (V - V_0)^2 (Peek's formula adapted for DC: frequency factor f removed; loss ∝ V(V - V_0)).
Influencing Factors
- Voltage: Loss ∝ V^2 (approx). HVDC lines (±800 kV, ±1100 kV) are highly susceptible.
- Conductor geometry: Bundle conductors (4–8 subconductors) increase effective radius, reducing surface gradient.
- Weather: Rain, fog, snow, hoarfrost drastically increase loss (up to 10–20x fair weather).
- Altitude: Lower air density reduces breakdown voltage; higher loss.
- Surface condition: Dust, bugs, corrosion points intensify corona.
Mitigation
- Conductor bundling: Standard for >400 kV.
- Corona rings / grading rings: Toroidal rings at hardware points redistribute field.
- Smooth surfaces: Aluminum-clad steel, careful installation.
- Optimized spacing: Phase-to-phase and phase-to-ground.
Impacts Beyond Loss
- Radio interference (RI): Broadband noise affects AM radio, comms.
- Audible noise (AN): Hissing/crackling; regulated near residences.
- Ozone/NOx production: Environmental concern.
Corona loss is a major design constraint for UHVDC (±800/1100 kV) lines.