In a PID (Proportional-Integral-Derivative) controller, the proportional band (PB) defines the range of input signal deviation around the setpoint over which the proportional term produces a proportional output change. It is the inverse of proportional gain (Kp).
PB (%) = (100 / Kp) × (Input Span / Output Span) — often simplified to PB = 100 / Kp when spans are normalized.
| Process Type | Typical PB Range | Reason |
|---|---|---|
| Temperature (slow, high lag) | 10–50% | Needs assertive action; integral handles lag |
| Flow (fast, low lag) | 50–200% | Sensitive; narrow PB causes valve chatter |
| Level (integrating process) | 100–500% | Very wide PB prevents cycling; I-term does the work |
| Pressure (moderate) | 20–100% | Balance speed vs. stability |
The proportional band is the primary sensitivity knob of a PID loop. Proper width balances responsiveness and stability. Always tune PB first, then I, then D—and validate with step tests under realistic load conditions.