How to Wire a Star-Delta (Wye-Delta) Motor Starter: Complete Wiring Guide
Safety first: Lockout/tagout power. Verify motor nameplate matches supply voltage. This guide covers standard 6-lead motor (T1–T6).
Terminal Identification
Motor leads typically labeled: U1, V1, W1, U2, V2, W2 (or T1–T6).
Wiring Steps
- Star (Wye) Run Contacts (KM1):
- Short U2, V2, W2 together (star point) — usually via bridge bar on contactor
- Connect supply L1→U1, L2→V1, L3→W1 via KM1 main poles
- Delta Run Contacts (KM2):
- Connect U1→V2, V1→W2, W1→U2 via KM2 main poles
- Control Circuit:
- Start button → KM1 coil + timer coil
- Timer (typically 5–10 sec) → drops KM1, picks KM2
- Interlock: KM1 & KM2 mechanically/electrically interlocked
- Overload relay in series with both contactor coils
- Power On: Close breaker; press Start. Motor runs star → transitions to delta
- Verify Rotation: If wrong, swap any two supply lines (L1/L2/L3)—not motor leads
Critical Checks
- Wire gauge per motor FLA + 125%
- Contactor ratings ≥ motor FLA
- Timer delay set for load inertia
- Ground motor frame
Always follow NEC/IEC/local codes and manufacturer diagrams.